Print
Devices for waterproofed roofs / HEXASTEEL DoP Eventail
HEXASTEEL DOP Foldable windshields (Double Flap, Pneumatic opening/closing) is a smoke and heat ventilator (NSHEV) for waterproofed roofs and is designed for overhead lighting and smoke ventilation.
HEXASTEEL DoP Foldable windshields features: a 300mm high metal upstand which can be equipped with a bitumen-coated insulation board to which the bitumen waterproofing membrane can be directly applied (heat loss coefficient: U = 2.5W/m²).
| Reference | Dimension (Low shafts) | Dimension (High shafts) | SLU m² | Upstand AFA 280mm | SGO | Angle d'ouverture | |
|---|---|---|---|---|---|---|---|
| C180 Standard | 180 x 180 | 180 x 180 | 3,24 | 2,20 | 3,24 | 90 | |
| C180 Plus | 180 x 180 | 180 x 180 | 3,24 | 2,43 | 3,24 | 90 | |
| C200 Standard | 200 x 200 | 200 x 200 | 4,00 | 2,72 | 4,00 | 90 | |
| C200 Plus | 200 x 200 | 200 x 200 | 4,00 | 3,00 | 4,00 | 90 | |
| R120 - 240 Plus | 120 x 240 | 120 x 240 | 2,88 | 2,16 | 2,88 | 90 | |
| R120 - 240 Standard | 120 x 240 | 120 x 240 | 2,88 | 2,02 | 2,88 | 90 | |
| R120 - 250 Plus | 120 x 250 | 120 x 250 | 3,00 | 2,25 | 3,00 | 90 | |
| R120 - 250 Standard | 120 x 250 | 120 x 250 | 3,00 | 1,53 | 3,00 | 90 | |
| R120 - 300 Standard | 120 x 300 | 120 x 300 | 3,60 | 2,48 | 3,60 | 90 | |
| R120 - 300 Plus | 120 x 300 | 120 x 300 | 3,60 | 2,70 | 3,60 | 90 | |
| R150 - 250 Standard | 150 x 250 | 150 x 250 | 3,75 | 2,55 | 3,75 | 90 | |
| R150 - 250 Plus | 150 x 250 | 150 x 250 | 3,75 | 2,81 | 3,75 | 90 | |
| R150 - 300 Standard | 150 x 300 | 150 x 300 | 4,50 | 3,06 | 4,50 | 90 | |
| R150 - 300 Plus | 150 x 300 | 150 x 300 | 4,50 | 3,38 | 4,50 | 90 | |
| R160 - 250 Standard | 160 x 250 | 160 x 250 | 4,00 | 2,72 | 4,00 | 90 | |
| R160 - 250 Plus | 160 x 250 | 160 x 250 | 4,00 | 3,00 | 4,00 | 90 | |
| R160 - 300 Plus | 160 x 300 | 160 x 300 | 4,80 | 3,61 | 4,80 | 90 | |
| R160 - 300 Standard | 160 x 300 | 160 x 300 | 4,80 | 3,26 | 4,80 | 90 | |
| R180 - 250 Plus | 180 x 250 | 180 x 250 | 4,50 | 3,39 | 4,50 | 90 | |
| R180 - 250 Standard | 180 x 250 | 180 x 250 | 4,50 | 3,06 | 4,50 | 90 | |
| R180 - 300 Standard | 180 x 300 | 180 x 300 | 5,40 | 3,67 | 5,40 | 90 | |
| R180 - 300 Plus | 180 x 300 | 180 x 300 | 5,40 | 4,09 | 5,40 | 90 | |
| R200 - 250 Standard | 200 x 250 | 200 x 250 | 5,00 | 3,40 | 5,00 | 90 | |
| R200 - 250 Plus | 200 x 250 | 200 x 250 | 5,00 | 3,78 | 5,00 | 90 | |
| R200 - 300 Standard | 200 x 300 | 200 x 300 | 6,00 | 4,08 | 6,00 | 90 | |
| R200 - 300 Plus | 200 x 300 | 200 x 300 | 6,00 | 4,56 | 6,00 | 90 | |
| Reference | Activation pressure | Thermal fuse cartridge weight in grams | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| PCA | CAI/DD | PCA | CAI/DD | ||||||||||
| SL 250 | SL 550 | SL 250 | SL 550 | SL 250 | SL 550 | SL 250 | SL 550 | ||||||
| Vol. total | Pression (bar) | Vol. total | Pression (bar) | Vol. total | Pression (bar) | Vol. total | Pression (bar) | Gramme (g.) | Gramme (g.) | Gramme (g.) | Gramme (g.) | ||
| C180 Standard | 1,14 | 10 | 1,14 | 15 | 1,14 | 10 | 1,14 | 16 | 20 | 20 | 20 | 20 | |
| C180 Plus | 1,14 | 10 | 1,14 | 15 | 1,14 | 10 | 1,14 | 16 | 20 | 20 | 20 | 20 | |
| C200 Standard | 1,3 | 10 | 1,3 | 18 | 1,3 | 12 | 1,3 | 20 | 20 | 40 | 20 | 40 | |
| C200 Plus | 1,3 | 10 | 1,3 | 18 | 1,3 | 12 | 1,3 | 20 | 20 | 40 | 20 | 40 | |
| R120 - 240 Plus | 0,62 | 10 | 0,62 | 17 | 0,62 | 11 | 0,62 | 19 | 20 | 20 | 20 | 20 | |
| R120 - 240 Standard | 0,62 | 10 | 0,62 | 17 | 0,62 | 11 | 0,62 | 19 | 20 | 20 | 20 | 20 | |
| R120 - 250 Plus | 0,62 | 10 | 0,62 | 18 | 0,62 | 11 | 0,62 | 20 | 20 | 20 | 20 | 20 | |
| R120 - 250 Standard | 0,62 | 10 | 0,62 | 18 | 0,62 | 11 | 0,62 | 20 | 20 | 20 | 20 | 20 | |
| R120 - 300 Standard | 0,62 | 11 | 0,62 | 21 | 0,62 | 13 | 0,62 | 23 | 20 | 20 | 20 | 20 | |
| R120 - 300 Plus | 0,62 | 11 | 0,62 | 21 | 0,62 | 13 | 0,62 | 23 | 20 | 20 | 20 | 20 | |
| R150 - 250 Standard | 0,86 | 10 | 0,86 | 16 | 0,86 | 11 | 0,86 | 18 | 20 | 20 | 20 | 20 | |
| R150 - 250 Plus | 0,86 | 10 | 0,86 | 16 | 0,86 | 11 | 0,86 | 18 | 20 | 20 | 20 | 20 | |
| R150 - 300 Standard | 0,86 | 10 | 0,86 | 19 | 0,86 | 12 | 0,86 | 21 | 20 | 20 | 20 | 20 | |
| R150 - 300 Plus | 0,86 | 10 | 0,86 | 19 | 0,86 | 12 | 0,86 | 21 | 20 | 20 | 20 | 20 | |
| R160 - 250 Standard | 1,02 | 10 | 1,02 | 16 | 1,02 | 10 | 1,02 | 18 | 20 | 20 | 20 | 20 | |
| R160 - 250 Plus | 1,02 | 10 | 1,02 | 16 | 1,02 | 10 | 1,02 | 18 | 20 | 20 | 20 | 20 | |
| R160 - 300 Plus | 1,02 | 10 | 1,02 | 19 | 1,02 | 12 | 1,02 | 21 | 20 | 40 | 20 | 40 | |
| R160 - 300 Standard | 1,02 | 10 | 1,02 | 19 | 1,02 | 12 | 1,02 | 21 | 20 | 40 | 20 | 40 | |
| R180 - 250 Plus | 1,14 | 10 | 1,14 | 19 | 1,14 | 12 | 1,14 | 21 | 20 | 40 | 20 | 40 | |
| R180 - 250 Standard | 1,14 | 10 | 1,14 | 19 | 1,14 | 12 | 1,14 | 21 | 20 | 40 | 20 | 40 | |
| R180 - 300 Standard | 1,14 | 12 | 1,14 | 22 | 1,14 | 14 | 1,14 | 25 | 20 | 40 | 20 | 40 | |
| R180 - 300 Plus | 1,14 | 12 | 1,14 | 22 | 1,14 | 14 | 1,14 | 25 | 20 | 40 | 20 | 40 | |
| R200 - 250 Standard | 1,3 | 12 | 1,3 | 22 | 1,3 | 14 | 2,04 | 16 | 20 | 40 | 20 | 40 | |
| R200 - 250 Plus | 1,3 | 12 | 1,3 | 22 | 1,3 | 14 | 2,04 | 16 | 20 | 40 | 20 | 40 | |
| R200 - 300 Standard | 1,3 | 14 | 2,04 | 17 | 1,3 | 17 | 2,04 | 18 | 20 | 40 | 40 | 40 | |
| R200 - 300 Plus | 1,3 | 14 | 2,04 | 17 | 1,3 | 17 | 2,04 | 18 | 20 | 40 | 40 | 40 | |
Aluminium cover
- Insulated, light transmission = 0%, heat loss coefficient U = 1.18 W/m².K.
- Non-insulated, light transmission = 0%.
PCA 10 mm Download PV fire
- Opal (B-S1 d0), light transmission = 62%, heat loss coefficient U = 3.1 W/m².K.
- Transparent (B-S1 d0), light transmission = 85%, heat loss coefficient U = 3.1 W/m².K.
- Calor control (B-S1 d0), light transmission = 55%, heat loss coefficient U = 3.1 W/m².K.
- Grey opaque, light transmission = 0%, heat loss coefficient U = 3.1 W/m².K.
PCA 16 mm Download PV fire
- Opal (B-S2 d0), light transmission = 51%, heat loss coefficient U = 2.8 W/m².K.
- Transparent (B-S2 d0), light transmission = 74%, heat loss coefficient U = 2.4 W/m².K.
- Calor control (B-S2 d0), light transmission = 46%, heat loss coefficient U = 2,4 W/m².K.
C02 thermofuse
- Rated to trip at 93°C (as standard and factory-assembled, delivered with CO2 cartridge).
Double flap
- Double-leaf device
Electrical switches
- They can be connected to an indicating panel showing the installation's opening position and functional status.
Griddle Download PV 1200j
- Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests).
Painted griddle Download PV 1200j
- Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests). RAL tint to be specified in the order.
Painted upstand
- The inside of the upstand can be painted. RAL tint to be specified in the order.
Part-opening electrical daily ventilation
- Partial ventilation 300mm with a cylinder (220V)
SL 250 snow load
- Regulatory snow load for smoke extraction in buildings located between 0 and 400m in altitude. SL 250 = 25 daN/m².
SL 550 snow load
- To exceed regulatory requirements. SL 500 minimum for buildings located between 400 and 800m in altitude.
Upstand for PVC membrane
- Upstand with factory-assembled unbacked insulation board compatible with a PVC membrane. Option to attach a strip of galvanised or PVC-coated steel at the top of the skylight frame.
C02 thermofuse
- Rated to trip at 93°C (as standard and factory-assembled, delivered with CO2 cartridge).
Double flap
- Double-leaf device
Electrical switches
- They can be connected to an indicating panel showing the installation's opening position and functional status.
Griddle
- Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests).
Painted griddle
- Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests). RAL tint to be specified in the order.
Painted upstand
- The inside of the upstand can be painted. RAL tint to be specified in the order.
Part-opening electrical daily ventilation
- Partial ventilation 300mm with a cylinder (220V)
SL 250 snow load
- Regulatory snow load for smoke extraction in buildings located between 0 and 400m in altitude. SL 250 = 25 daN/m².
SL 550 snow load
- To exceed regulatory requirements. SL 500 minimum for buildings located between 400 and 800m in altitude.
Upstand for PVC membrane
- Upstand with factory-assembled unbacked insulation board compatible with a PVC membrane. Option to attach a strip of galvanised or PVC-coated steel at the top of the skylight frame.