HEXASTEEL MOE (Single Flap, Electric opening/closing) is a smoke and heat ventilator (NSHEV) for waterproofed roofs and is designed for overhead lighting and smoke extraction.
HEXASTEEL MoE features: a 300mm high metal upstand which can be equipped with a bitumen-coated insulation board to which the bitumen waterproofing membrane can be directly applied (heat loss coefficient: U = 2.5W/m²).
| Reference | Dimension (Low shafts) | Dimension (High shafts) | SLU m² | Upstand AFA 280mm | SGO | Weight | Angle d'ouverture | |
|---|---|---|---|---|---|---|---|---|
| R120-200 Plus | 120 x 200 | 120 x 200 | - | 1,78 | 2,40 | - | - | |
| R120-160 Eco | 120 x 160 | 120 x 160 | - | 0,96 | 1,92 | - | - | |
| R120-180 Plus | 120 x 180 | 120 x 180 | - | 1,60 | 2,16 | - | - | |
| R120-200 Eco | 120 x 200 | 120 x 200 | - | 1,20 | 2,40 | - | - | |
| R120-180 Eco | 120 x 180 | 120 x 180 | - | 1,08 | 2,16 | - | - | |
| R120-250 Plus | 120 x 250 | 120 x 250 | - | 2,07 | 3,00 | - | - | |
| R120-160 Standard | 120 x 160 | 120 x 160 | - | 1,25 | 1,92 | - | - | |
| R120-250 Eco | 120 x 250 | 120 x 250 | - | 1,35 | 3,00 | - | - | |
| R120-200 Standard | 120 x 200 | 120 x 200 | - | 1,58 | 2,40 | - | - | |
| R120-180 Standard | 120 x 180 | 120 x 180 | - | 1,42 | 2,16 | - | - | |
| R120-160 Plus | 120 x 160 | 120 x 160 | - | 1,42 | 1,92 | - | - | |
| R120-250 Standard | 120 x 250 | 120 x 250 | - | 1,92 | 3,00 | - | - | |
| C130 Eco | 130 x 130 | 130 x 130 | - | 0,85 | 1,69 | - | - | |
| C130 Plus | 130 x 130 | 130 x 130 | - | 1,25 | 1,69 | - | - | |
| R140-200 Standard | 140 x 200 | 140 x 200 | - | 1,85 | 2,80 | - | - | |
| R140-200 Plus | 140 x 200 | 140 x 200 | - | 2,02 | 2,80 | - | - | |
| C130 Standard | 130 x 130 | 130 x 130 | - | 1,10 | 1,69 | - | - | |
| C100 Standard | 100 x 100 | 100 x 100 | 1,00 | 0,69 | 1,00 | 62 | 165 | |
| C100 Plus | 100 x 100 | 100 x 100 | 1,00 | 0,74 | 1,00 | 70 | 165 | |
| C100 Eco | 100 x 100 | 100 x 100 | 1,00 | 0,50 | 1,00 | 59 | 165 | |
| C120 Eco | 120 x 120 | 120 x 120 | 1,44 | 0,72 | 1,44 | 73 | 165 | |
| C120 Standard | 120 x 120 | 120 x 120 | 1,44 | 0,96 | 1,44 | 76 | 165 | |
| C120 Plus | 120 x 120 | 120 x 120 | 1,44 | 1,07 | 1,44 | 85 | 165 | |
| C140 Plus | 140 x 140 | 140 x 140 | 1,96 | 1,45 | 1,96 | 104 | 165 | |
| C140 Eco | 140 x 140 | 140 x 140 | 1,96 | 0,98 | 1,96 | 85 | 165 | |
| C140 Standard | 140 x 140 | 140 x 140 | 1,96 | 1,28 | 1,96 | 93 | 165 | |
| R140-200Eco | 140 x 200 | 140 x 200 | - | 1,40 | 2,80 | - | - | |
| R100-140 Plus | 100 x 140 | 100 x 140 | 1,40 | 1,04 | 1,40 | 84 | 165 | |
| R100-140 Eco | 100 x 140 | 100 x 140 | 1,40 | 0,70 | 1,40 | 72 | 165 | |
| R100-140 Standard | 100 x 140 | 100 x 140 | 1,40 | 0,93 | 1,40 | 75 | 165 | |
| R100-150 Standard | 100 x 150 | 100 x 150 | 1,50 | 0,99 | 1,50 | 79 | 165 | |
| R100-150 Plus | 100 x 150 | 100 x 150 | 1,50 | 1,11 | 1,50 | 88 | 165 | |
| R100-150 Eco | 100 x 150 | 100 x 150 | 1,50 | 0,75 | 1,50 | 76 | 165 | |
| R100-200 Standard | 100 x 200 | 100 x 200 | 2,00 | 1,30 | 2,00 | 90 | 165 | |
| R100-200 Plus | 100 x 200 | 100 x 200 | 2,00 | 1,48 | 2,00 | 102 | 165 | |
| R100-200 Eco | 100 x 200 | 100 x 200 | 2,00 | 1,00 | 2,00 | 87 | 165 |
Aluminium cover
- Insulated, light transmission = 0%, heat loss coefficient U = 1.18 W/m².K.
- Non-insulated, light transmission = 0%.
Double dome Download PV fire
- Opal/Transparent (M4 non-dripping) light transmission = 70%, heat loss coefficient U = 2,8 W/m².K.
PCA 10 mm Download PV fire
- Opal (B-S1 d0), light transmission = 62%, heat loss coefficient U = 3.1 W/m².K.
- Transparent (B-S1 d0), light transmission = 85%, heat loss coefficient U = 3.1 W/m².K.
- Calor control (B-S1 d0), light transmission = 55%, heat loss coefficient U = 3.1 W/m².K.
- Grey opaque, light transmission = 0%, heat loss coefficient U = 3.1 W/m².K.
PCA 16 mm Download PV fire
- Opal (B-S2 d0), light transmission = 51%, heat loss coefficient U = 2.8 W/m².K.
- Transparent (B-S2 d0), light transmission = 74%, heat loss coefficient U = 2.4 W/m².K.
- Calor control (B-S2 d0), light transmission = 46%, heat loss coefficient U = 2,4 W/m².K.
Electrical switches
- They can be connected to an indicating panel showing the installation's opening position and functional status.
Griddle Download PV 1200j
- Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests).
Painted griddle Download PV 1200j
- Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests). RAL tint to be specified in the order.
Painted upstand
- The inside of the upstand can be painted. RAL tint to be specified in the order.
Single flap
- Single-leaf device
SL 250 snow load
- Regulatory snow load for smoke extraction in buildings located between 0 and 400m in altitude. SL 250 = 25 daN/m².
SL 550 snow load
- To exceed regulatory requirements. SL 500 minimum for buildings located between 400 and 800m in altitude.
Upstand for PVC membrane
- Upstand with factory-assembled unbacked insulation board compatible with a PVC membrane. Option to attach a strip of galvanised or PVC-coated steel at the top of the skylight frame.
Electrical switches
- They can be connected to an indicating panel showing the installation's opening position and functional status.
Griddle
- Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests).
Painted griddle
- Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests). RAL tint to be specified in the order.
Painted upstand
- The inside of the upstand can be painted. RAL tint to be specified in the order.
Single flap
- Single-leaf device
SL 250 snow load
- Regulatory snow load for smoke extraction in buildings located between 0 and 400m in altitude. SL 250 = 25 daN/m².
SL 550 snow load
- To exceed regulatory requirements. SL 500 minimum for buildings located between 400 and 800m in altitude.
Upstand for PVC membrane