Devices for waterproofed roofs / HEXASTEEL MOE

Smoke extraction - HEXASTEEL MOE
Download
HEXASTEEL MOE (Single Flap, Electric opening/closing) is a smoke and heat ventilator (NSHEV) for waterproofed roofs and is designed for overhead lighting and smoke extraction.

HEXASTEEL MoE features: a 300mm high metal upstand which can be equipped with a bitumen-coated insulation board to which the bitumen waterproofing membrane can be directly applied (heat loss coefficient: U = 2.5W/m²).

   
ReferenceDimension (Low shafts)Dimension (High shafts)SLU m²Upstand AFA 280mmSGOWeightAngle d'ouverture
R120-200 Plus 120 x 200 120 x 200- 1,78 2,40--
R120-160 Eco 120 x 160 120 x 160- 0,96 1,92--
R120-180 Plus 120 x 180 120 x 180- 1,60 2,16--
R120-200 Eco 120 x 200 120 x 200- 1,20 2,40--
R120-180 Eco 120 x 180 120 x 180- 1,08 2,16--
R120-250 Plus 120 x 250 120 x 250- 2,07 3,00--
R120-160 Standard 120 x 160 120 x 160- 1,25 1,92--
R120-250 Eco 120 x 250 120 x 250- 1,35 3,00--
R120-200 Standard 120 x 200 120 x 200- 1,58 2,40--
R120-180 Standard 120 x 180 120 x 180- 1,42 2,16--
R120-160 Plus 120 x 160 120 x 160- 1,421,92--
R120-250 Standard 120 x 250 120 x 250- 1,92 3,00--
C130 Eco 130 x 130 130 x 130- 0,85 1,69--
C130 Plus 130 x 130 130 x 130- 1,25 1,69--
R140-200 Standard 140 x 200 140 x 200- 1,85 2,80--
R140-200 Plus 140 x 200 140 x 200- 2,022,80--
C130 Standard 130 x 130 130 x 130- 1,10 1,69--
C100 Standard100 x 100100 x 1001,000,691,0062165
C100 Plus100 x 100100 x 1001,000,741,0070165
C100 Eco100 x 100100 x 1001,000,501,0059165
C120 Eco120 x 120120 x 1201,440,721,4473165
C120 Standard120 x 120120 x 1201,440,961,4476165
C120 Plus120 x 120120 x 1201,441,071,4485165
C140 Plus140 x 140140 x 1401,961,451,96104165
C140 Eco140 x 140140 x 1401,960,981,9685165
C140 Standard140 x 140140 x 1401,961,281,9693165
R140-200Eco 140 x 200 140 x 200- 1,40 2,80--
R100-140 Plus100 x 140100 x 1401,401,041,4084165
R100-140 Eco100 x 140100 x 1401,400,701,4072165
R100-140 Standard100 x 140100 x 1401,400,931,4075165
R100-150 Standard100 x 150100 x 1501,500,991,5079165
R100-150 Plus100 x 150100 x 1501,501,111,5088165
R100-150 Eco100 x 150100 x 1501,500,751,5076165
R100-200 Standard100 x 200100 x 2002,001,302,0090165
R100-200 Plus100 x 200100 x 2002,001,482,00102165
R100-200 Eco100 x 200100 x 2002,001,002,0087165

Aluminium cover

  • Insulated, light transmission = 0%, heat loss coefficient U = 1.18 W/m².K.
  • Non-insulated, light transmission = 0%.

Double dome  Download PV fire

  • Opal/Transparent (M4 non-dripping) light transmission = 70%, heat loss coefficient U = 2,8 W/m².K.

PCA 10 mm  Download PV fire

  • Opal (B-S1 d0), light transmission = 62%, heat loss coefficient U = 3.1 W/m².K.
  • Transparent (B-S1 d0), light transmission = 85%, heat loss coefficient U = 3.1 W/m².K.
  • Calor control (B-S1 d0), light transmission = 55%, heat loss coefficient U = 3.1 W/m².K.
  • Grey opaque, light transmission = 0%, heat loss coefficient U = 3.1 W/m².K.

PCA 16 mm  Download PV fire

  • Opal (B-S2 d0), light transmission = 51%, heat loss coefficient U = 2.8 W/m².K.
  • Transparent (B-S2 d0), light transmission = 74%, heat loss coefficient U = 2.4 W/m².K.
  • Calor control (B-S2 d0), light transmission = 46%, heat loss coefficient U = 2,4 W/m².K.

Electrical switches

  • They can be connected to an indicating panel showing the installation's opening position and functional status.

Griddle  Download PV 1200j

  • Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests).

Painted griddle  Download PV 1200j

  • Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests). RAL tint to be specified in the order.

Painted upstand

  • The inside of the upstand can be painted. RAL tint to be specified in the order.

Single flap

  • Single-leaf device

SL 250 snow load

  • Regulatory snow load for smoke extraction in buildings located between 0 and 400m in altitude. SL 250 = 25 daN/m².

SL 550 snow load

  • To exceed regulatory requirements. SL 500 minimum for buildings located between 400 and 800m in altitude.

Upstand for PVC membrane

  • Upstand with factory-assembled unbacked insulation board compatible with a PVC membrane. Option to attach a strip of galvanised or PVC-coated steel at the top of the skylight frame.

Electrical switches

  • They can be connected to an indicating panel showing the installation's opening position and functional status.

Griddle

  • Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests).

Painted griddle

  • Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests). RAL tint to be specified in the order.

Painted upstand

  • The inside of the upstand can be painted. RAL tint to be specified in the order.

Single flap

  • Single-leaf device

SL 250 snow load

  • Regulatory snow load for smoke extraction in buildings located between 0 and 400m in altitude. SL 250 = 25 daN/m².

SL 550 snow load

  • To exceed regulatory requirements. SL 500 minimum for buildings located between 400 and 800m in altitude.

Upstand for PVC membrane

  • Upstand with factory-assembled unbacked insulation board compatible with a PVC membrane. Option to attach a strip of galvanised or PVC-coated steel at the top of the skylight frame.