Hexadome
111 1111
Print

Smoke extraction

Devices for waterproofed roofs / HEXASTEEL MoP biais

HEXASTEEL MOP oblique (Single Flap, Pneumatic opening/closing) is a smoke and heat ventilator (NSHEV) for waterproofed roofs and is designed for overhead lighting and smoke extraction.

HEXASTEEL MoP oblique features: a 300mm high metal upstand which can be equipped with a bitumen-coated insulation board to which the bitumen waterproofing membrane can be directly applied (heat loss coefficient: U = 2.5W/m²).

   
ReferenceDimension (Low shafts)Dimension (High shafts)SLU m²Upstand AFA 280mmSGOWeightAngle d'ouverture
C100 Standard120 x 120100 x 1001,000,791,4466165  
C100 Eco120 x 120100 x 1001,000,721,4463165  
C120 Eco140 x 140120 x 1201,440,981,9675165  
C120 Standard140 x 140120 x 1201,441,131,9678165  
C130 Eco150 x 150130 x 1301,691,132,2582165  
C130 Standard150 x 150130 x 1301,691,322,2590165  
C140 Eco160 x 160140 x 1401,961,282,5692165  
C140 Standard160 x 160140 x 1401,961,532,56100165  
C150 Eco170 x 170150 x 1502,251,422,8998165  
C150 Standard170 x 170150 x 1502,251,762,89106165  
C160 Standard180 x 180160 x 1602,562,023,24113165  
C160 Eco180 x 180160 x 1602,561,563,24105165  
C180 Standard200 x 200180 x 1803,242,564,00144165  
C180 Eco200 x 200180 x 1803,241,764,00119165  
C200 Eco220 x 220200 x 2004,001,984,84133165  
C200 Standard220 x 220200 x 2004,003,154,84158165  
R100-140 Eco120 x 160100 x 1401,400,961,9275165  
R100-140 Standard120 x 160100 x 1401,401,141,9278165  
R100-150 Eco120 x 170100 x 1501,501,022,0478165  
R100-150 Standard120 x 170100 x 1501,501,222,0481165  
R100-200 Standard120 x 220100 x 2002,001,642,6497165  
R100-200 Eco120 x 220100 x 2002,001,322,6494165  
R120-160 Standard140 x 180120 x 1601,921,562,5291165  
R120-160 Eco140 x 180120 x 1601,921,262,5288165  
R120-180 Eco140 x 200120 x 1802,161,402,8094165  
R120-180 Standard140 x 200120 x 1802,161,742,80102165  
R120-200 Eco140 x 220120 x 2002,401,513,08101165  
R120-200 Standard140 x 220120 x 2002,401,913,08109165  
R140-200 Eco160 x 220140 x 2002,801,623,52112165  
R140-200 Standard160 x 220140 x 2002,802,223,52120165  
R160-200 Standard180 x 220160 x 2003,202,533,96127165  
R160-200 Eco180 x 220160 x 2003,201,743,96119165  

Reference Activation pressure Thermal fuse cartridge weight in grams
PCA CAI/DD PCA CAI/DD
SL 250 SL 550 SL 250 SL 550 SL 250 SL 550 SL 250 SL 550
Vol. total Pression (bar) Vol. total Pression (bar) Vol. total Pression (bar) Vol. total Pression (bar) Gramme (g.) Gramme (g.) Gramme (g.) Gramme (g.)
C100 Standard 0,67130,67220,67161,051720202020  
C100 Eco 0,67130,67220,67161,051720202020  
C120 Eco 0,67212,69101,05172,691120402040  
C120 Standard 0,67212,69101,05172,691120402040  
C130 Eco 1,05172,69122,69102,691420404040  
C130 Standard 1,05172,69122,69102,691420404040  
C140 Eco 1,6121,6224,11104,111020408080  
C140 Standard 1,6121,6224,11104,111020408080  
C150 Eco 1,6154,11114,11104,111240808080  
C150 Standard 1,6154,11114,11104,111240808080  
C160 Standard 2,69102,69192,69122,692180808080  
C160 Eco 2,69102,69192,69122,692180808080  
C180 Standard 2,69142,6926----8080--  
C180 Eco 2,69142,6926----8080--  
C200 Eco 4,34114,3421----8080--  
C200 Standard 4,34114,3421----8080--  
R100-140 Eco 0,67161,05191,05131,052220402040  
R100-140 Standard 0,67161,05191,05131,052220402040  
R100-150 Eco 0,67171,05201,05142,691020402040  
R100-150 Standard 0,67171,05201,05142,691020402040  
R100-200 Standard 0,67212,69101,05172,691220402040  
R100-200 Eco 0,67212,69101,05172,691220402040  
R120-160 Standard 1,05172,69132,69102,691420404040  
R120-160 Eco 1,05172,69132,69102,691420404040  
R120-180 Eco 1,05182,69142,69102,691620404080  
R120-180 Standard 1,05182,69142,69102,691620404080  
R120-200 Eco 1,05202,69152,69102,691740804080  
R120-200 Standard 1,05202,69152,69102,691740804080  
R140-200 Eco 1,6164,11124,11104,111440808080  
R140-200 Standard 1,6164,11124,11104,111440808080  
R160-200 Standard 2,69122,6923----8080--  
R160-200 Eco 2,69122,6923----8080--  

Aluminium cover

  • Insulated, light transmission = 0%, heat loss coefficient U = 1.18 W/m².K.
  • Non-insulated, light transmission = 0%.

Double dome  Download PV fire

  • Opal/Transparent (M4), light transmission = 70%, heat loss coefficient U = 2,8 W/m².K.
  • Opal/Transparent (M4 non-dripping) light transmission = 70%, heat loss coefficient U = 2,8 W/m².K.

PCA 10 mm  Download PV fire

  • Opal (B-S1 d0), light transmission = 62%, heat loss coefficient U = 3.1 W/m².K.
  • Transparent (B-S1 d0), light transmission = 85%, heat loss coefficient U = 3.1 W/m².K.
  • Calor control (B-S1 d0), light transmission = 55%, heat loss coefficient U = 3.1 W/m².K.
  • Grey opaque, light transmission = 0%, heat loss coefficient U = 3.1 W/m².K.

PCA 16 mm  Download PV fire

  • Opal (B-S2 d0), light transmission = 51%, heat loss coefficient U = 2.8 W/m².K.
  • Transparent (B-S2 d0), light transmission = 74%, heat loss coefficient U = 2.4 W/m².K.
  • Calor control (B-S2 d0), light transmission = 46%, heat loss coefficient U = 2,4 W/m².K.

C02 thermofuse

  • Rated to trip at 93°C (as standard and factory-assembled, delivered with CO2 cartridge).

Electrical switches

  • They can be connected to an indicating panel showing the installation's opening position and functional status.

Griddle  Download PV 1200j

  • Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests).

Painted griddle  Download PV 1200j

  • Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests). RAL tint to be specified in the order.

Painted upstand

  • The inside of the upstand can be painted. RAL tint to be specified in the order.

Part opening pneumatic daily ventilation

  • Partial ventilation 300mm with an optional extra cylinder (minimum pressure 6 bar, maximum pressure 8 bar)

Part-opening electrical daily ventilation

  • Partial ventilation 300mm with a cylinder (220V)

Pneumatic opening

  • Opening is controlled by a pneumatic cylinder.

Single flap

  • Single-leaf device

SL 250 snow load

  • Regulatory snow load for smoke extraction in buildings located between 0 and 400m in altitude. SL 250 = 25 daN/m².

SL 550 snow load

  • To exceed regulatory requirements. SL 500 minimum for buildings located between 400 and 800m in altitude.

Upstand for PVC membrane

  • Upstand with factory-assembled unbacked insulation board compatible with a PVC membrane. Option to attach a strip of galvanised or PVC-coated steel at the top of the skylight frame.

C02 thermofuse

  • Rated to trip at 93°C (as standard and factory-assembled, delivered with CO2 cartridge).

Electrical switches

  • They can be connected to an indicating panel showing the installation's opening position and functional status.

Griddle

  • Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests).

Painted griddle

  • Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests). RAL tint to be specified in the order.

Painted upstand

  • The inside of the upstand can be painted. RAL tint to be specified in the order.

Part opening pneumatic daily ventilation

  • Partial ventilation 300mm with an optional extra cylinder (minimum pressure 6 bar, maximum pressure 8 bar)

Part-opening electrical daily ventilation

  • Partial ventilation 300mm with a cylinder (220V)

Pneumatic opening

  • Opening is controlled by a pneumatic cylinder.

Single flap

  • Single-leaf device

SL 250 snow load

  • Regulatory snow load for smoke extraction in buildings located between 0 and 400m in altitude. SL 250 = 25 daN/m².

SL 550 snow load

  • To exceed regulatory requirements. SL 500 minimum for buildings located between 400 and 800m in altitude.

Upstand for PVC membrane

  • Upstand with factory-assembled unbacked insulation board compatible with a PVC membrane. Option to attach a strip of galvanised or PVC-coated steel at the top of the skylight frame.