Print
Devices for waterproofed roofs / HEXASTEEL MoT biais
HEXASTEEL MOT oblique (Single Flap, Winch opening/closing) is a smoke and heat ventilator (NSHEV) for waterproofed roofs and is designed for overhead lighting and smoke extraction.
HEXASTEEL MoT oblique features: a 300mm high metal upstand which can be equipped with a bitumen-coated insulation board to which the bitumen waterproofing membrane can be directly applied (heat loss coefficient: U = 2.5W/m²).
| Reference | Dimension (Low shafts) | Dimension (High shafts) | SLU m² | Upstand AFA 280mm | SGO | Weight | Angle d'ouverture | |
|---|---|---|---|---|---|---|---|---|
| C100 Standard | 120 x 120 | 100 x 100 | 1,00 | 0,79 | 1,44 | 60 | 160 | |
| C100 Eco | 120 x 120 | 100 x 100 | 1,00 | 0,72 | 1,44 | 57 | 160 | |
| C120 Eco | 140 x 140 | 120 x 120 | 1,44 | 0,98 | 1,96 | 70 | 160 | |
| C120 Standard | 140 x 140 | 120 x 120 | 1,44 | 1,13 | 1,96 | 73 | 160 | |
| C130 Eco | 150 x 150 | 130 x 130 | 1,69 | 1,13 | 2,25 | 76 | 160 | |
| C130 Standard | 150 x 150 | 130 x 130 | 1,69 | 1,32 | 2,25 | 84 | 160 | |
| C140 Eco | 160 x 160 | 140 x 140 | 1,96 | 1,28 | 2,56 | 82 | 160 | |
| C140 Standard | 160 x 160 | 140 x 140 | 1,96 | 1,53 | 2,56 | 90 | 160 | |
| R100-140 Eco | 120 x 160 | 100 x 140 | 1,40 | 0,96 | 1,92 | 70 | 160 | |
| R100-140 Standard | 120 x 160 | 100 x 140 | 1,40 | 1,14 | 1,92 | 73 | 160 | |
| R100-150 Standard | 120 x 170 | 100 x 150 | 1,50 | 1,22 | 2,04 | 76 | 160 | |
| R100-150 Eco | 120 x 170 | 100 x 150 | 1,50 | 1,02 | 2,04 | 73 | 160 | |
| R100-200 Standard | 120 x 220 | 100 x 200 | 2,00 | 1,64 | 2,64 | 91 | 160 | |
| R100-200 Eco | 120 x 220 | 100 x 200 | 2,00 | 1,24 | 2,64 | 88 | 160 | |
| R120-160 Eco | 140 x 180 | 120 x 160 | 1,92 | 1,23 | 2,52 | 82 | 160 | |
| R120-160 Standard | 140 x 180 | 120 x 160 | 1,92 | 1,56 | 2,52 | 90 | 160 | |
| R120-180 Eco | 140 x 200 | 120 x 180 | 2,16 | 1,34 | 2,80 | 88 | 160 | |
| R120-180 Standard | 140 x 200 | 120 x 180 | 2,16 | 1,74 | 2,80 | 96 | 160 | |
| R120-200 Eco | 140 x 220 | 120 x 200 | 2,40 | 1,42 | 3,08 | 94 | 160 | |
| R120-200 Standard | 140 x 220 | 120 x 200 | 2,40 | 1,91 | 3,08 | 102 | 160 | |
| Reference | Activation pressure | ||||
|---|---|---|---|---|---|
| PCA | CAI/DD | ||||
| SL 250 | SL 500 | SL 250 | SL 500 | ||
| C100 Standard | x | x | x | x | |
| C100 Eco | x | x | x | x | |
| C120 Eco | x | x | x | | |
| C120 Standard | x | x | x | | |
| C130 Eco | x | x | | ||
| C130 Standard | x | x | | ||
| C140 Eco | x | | |||
| C140 Standard | x | | |||
| R100-140 Eco | x | x | | ||
| R100-140 Standard | x | x | | ||
| R100-150 Standard | x | x | | ||
| R100-150 Eco | x | x | | ||
| R100-200 Standard | x | x | | ||
| R100-200 Eco | x | x | | ||
| R120-160 Eco | x | | |||
| R120-160 Standard | x | | |||
| R120-180 Eco | x | | |||
| R120-180 Standard | x | | |||
| R120-200 Eco | x | | |||
| R120-200 Standard | x | | |||
Aluminium cover
- Insulated, light transmission = 0%, heat loss coefficient U = 1.18 W/m².K.
- Non-insulated, light transmission = 0%.
Double dome Download PV fire Download PV 1200j
- Opal/Transparent (M4), light transmission = 70%, heat loss coefficient U = 2,8 W/m².K.
- Opal/Transparent (M4 non-dripping) light transmission = 70%, heat loss coefficient U = 2,8 W/m².K.
- HEXACHOC 1200 Joules, Transparent/Opal (M4 non-dripping) light transmission = 70%, heat loss coefficient U = 2,8 W/m².K.
PCA 10 mm Download PV fire
- Opal (B-S1 d0), light transmission = 62%, heat loss coefficient U = 3.1 W/m².K.
- Transparent (B-S1 d0), light transmission = 85%, heat loss coefficient U = 3.1 W/m².K.
- Calor control (B-S1 d0), light transmission = 55%, heat loss coefficient U = 3.1 W/m².K.
- Grey opaque, light transmission = 0%, heat loss coefficient U = 3.1 W/m².K.
PCA 16 mm Download PV fire
- Opal (B-S2 d0), light transmission = 51%, heat loss coefficient U = 2.8 W/m².K.
- Transparent (B-S2 d0), light transmission = 74%, heat loss coefficient U = 2.4 W/m².K.
- Calor control (B-S2 d0), light transmission = 46%, heat loss coefficient U = 2,4 W/m².K.
Electrical switches
- They can be connected to an indicating panel showing the installation's opening position and functional status.
Griddle Download PV 1200j
- Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests).
Painted griddle Download PV 1200j
- Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests). RAL tint to be specified in the order.
Painted upstand
- The inside of the upstand can be painted. RAL tint to be specified in the order.
Single flap
- Single-leaf device
SL 250 snow load
- Regulatory snow load for smoke extraction in buildings located between 0 and 400m in altitude. SL 250 = 25 daN/m².
SL 500 snow load
- Regulatory snow load for smoke extraction in buildings located between 400 and 800m in altitude. SL 500 = 50 daN/m².
Thermal fuse
- Rated to trip at 93°C (as standard).
Upstand for PVC membrane
- Upstand with factory-assembled unbacked insulation board compatible with a PVC membrane. Option to attach a strip of galvanised or PVC-coated steel at the top of the skylight frame.
Winch opening
- Opening is controlled by a winch box.
Electrical switches
- They can be connected to an indicating panel showing the installation's opening position and functional status.
Griddle
- Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests).
Painted griddle
- Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests). RAL tint to be specified in the order.
Painted upstand
- The inside of the upstand can be painted. RAL tint to be specified in the order.
Single flap
- Single-leaf device
SL 250 snow load
- Regulatory snow load for smoke extraction in buildings located between 0 and 400m in altitude. SL 250 = 25 daN/m².
SL 500 snow load
- Regulatory snow load for smoke extraction in buildings located between 400 and 800m in altitude. SL 500 = 50 daN/m².
Thermal fuse
- Rated to trip at 93°C (as standard).
Upstand for PVC membrane
- Upstand with factory-assembled unbacked insulation board compatible with a PVC membrane. Option to attach a strip of galvanised or PVC-coated steel at the top of the skylight frame.
Winch opening
- Opening is controlled by a winch box.