Vaults / HEXAVOUTE DOP
HEXAVOUTE DOP (Double Flap, pneumatic opening/closing) is a smoke and heat ventilator (NSHEV) built into a skybelt and is designed for overhead lighting and smoke extraction.
HEXAVOUTE DOP features: self-supporting bent extruded unwrought aluminium profiles (lower and upper arches) spaced approximately 0.7 or 1 metre apart, extruded unwrought aluminium side profiles (gutters), aluminium capping strips, stainless steel screws,
| Reference | Dimension (High shafts) | SLU m² | Upstand AFA 280mm | SGO | Angle d'ouverture | |
| 150-200 | 150 x 200 | 3,00 | 1,64 | 3,00 | 90 | |
| 150-300 | 150 x 300 | 4,50 | 2,25 | 4,50 | 90 | |
| 200-100 | 200 x 100 | 2,00 | 1,02 | 1,70 | 90 | |
| 200-200 | 200 x 200 | 4,00 | 2,19 | 4,00 | 90 | |
| 200-300 | 200 x 300 | 6,00 | 3,03 | 6,00 | 90 | |
| 250-100 | 250 x 100 | 2,50 | 1,30 | 2,13 | 90 | |
| 250-200 | 250 x 200 | 5,00 | 2,75 | 5,00 | 90 | |
| 300-100 | 300 x 100 | 3,00 | 1,53 | 2,55 | 90 | |
| 300-200 | 300 x 200 | 6,00 | 3,28 | 6,00 | 90 | |
| Reference |
Activation pressure |
Thermal fuse cartridge weight in grams |
|
| PCA |
CAI/DD |
PCA |
CAI/DD |
| SL 250 |
SL 550 |
SL 250 |
SL 550 |
SL 250 |
SL 550 |
SL 250 |
SL 550 |
| Vol. total |
Pression (bar) |
Vol. total |
Pression (bar) |
Vol. total |
Pression (bar) |
Vol. total |
Pression (bar) |
Gramme (g.) |
Gramme (g.) |
Gramme (g.) |
Gramme (g.) |
| 150-200 |
0,86 | 10 | 0,86 | 14 | 0,86 | 10 | 0,86 | 15 | 20 | 20 | 20 | 20 | |
| 150-300 |
0,86 | 10 | 0,86 | 19 | 0,86 | 12 | 0,86 | 21 | 20 | 20 | 20 | 20 | |
| 200-100 |
1,31 | 10 | 1,31 | 12 | | | | | 20 | 20 | 20 | 20 | |
| 200-200 |
1,3 | 10 | 1,3 | 18 | 1,3 | 12 | 1,3 | 20 | 20 | 40 | 20 | 40 | |
| 200-300 |
1,3 | 14 | 2,04 | 17 | 1,3 | 17 | 2,04 | 18 | 20 | 40 | 40 | 40 | |
| 250-100 |
1,63 | 10 | 1,63 | 15 | | | | | 20 | 20 | 20 | 20 | |
| 250-200 |
1,63 | 11 | 1,63 | 22 | | | | | 40 | 40 | 40 | 40 | |
| 300-100 |
2,01 | 10 | 2,01 | 17 | | | | | 40 | 40 | 40 | 40 | |
| 300-200 |
2,01 | 12 | 2,01 | 23 | | | | | 40 | 40 | 40 | 40 | |
- Opal (B-S1 d0), light transmission = 62%, heat loss coefficient U = 3.1 W/m².K.
- Transparent (B-S1 d0), light transmission = 85%, heat loss coefficient U = 3.1 W/m².K.
- Calor control (B-S1 d0), light transmission = 55%, heat loss coefficient U = 3.1 W/m².K.
- Opal (B-S2 d0), light transmission = 51%, heat loss coefficient U = 2.8 W/m².K.
- Transparent (B-S2 d0), light transmission = 74%, heat loss coefficient U = 2.4 W/m².K.
- Calor control (B-S2 d0), light transmission = 46%, heat loss coefficient U = 2,4 W/m².K.
C02 thermofuse
- Rated to trip at 93°C (as standard and factory-assembled, delivered with CO2 cartridge).
Double flap
Electrical switches
- They can be connected to an indicating panel showing the installation's opening position and functional status.
Pneumatic opening
- Opening is controlled by a pneumatic cylinder.
SL 250 snow load
- Regulatory snow load for smoke extraction in buildings located between 0 and 400m in altitude. SL 250 = 25 daN/m².
SL 550 snow load
- To exceed regulatory requirements. SL 500 minimum for buildings located between 400 and 800m in altitude.
C02 thermofuse
- Rated to trip at 93°C (as standard and factory-assembled, delivered with CO2 cartridge).
Double flap
Electrical switches
- They can be connected to an indicating panel showing the installation's opening position and functional status.
Pneumatic opening
- Opening is controlled by a pneumatic cylinder.
SL 250 snow load
- Regulatory snow load for smoke extraction in buildings located between 0 and 400m in altitude. SL 250 = 25 daN/m².
SL 550 snow load
- To exceed regulatory requirements. SL 500 minimum for buildings located between 400 and 800m in altitude.