Devices for dry roofs / HEXAONDE MoP
HEXAONDE MOP (Single Flap, Pneumatic opening/closing) is a smoke and heat ventilator (NSHEV) for dry roofs and is designed for overhead lighting and smoke extraction.
HEXAONDE MoP features a smoke vent built into a polyester profiled upstand reinforced with tinted fibreglass (steel or aluminium cladding: RAL 9010, fibre cement: RAL 7040).
| Reference | Dimension (Low shafts) | Dimension (High shafts) | SLU m² | Upstand AFA 280mm | SGO | Weight | Angle d'ouverture | |
| C100 Eco | 120 x 120 | 100 x 100 | 1,00 | 0,72 | 1,44 | 62 | 165 | |
| C100 Standard | 120 x 120 | 100 x 100 | 1,00 | 0,88 | 1,44 | 65 | 165 | |
| C120 Eco | 140 x 140 | 120 x 120 | 1,44 | 0,98 | 1,96 | 74 | 165 | |
| C120 Standard | 140 x 140 | 120 x 120 | 1,44 | 1,20 | 1,96 | 79 | 165 | |
| C140 Standard | 160 x 160 | 140 x 140 | 1,96 | 1,56 | 2,56 | 95 | 165 | |
| C140 Eco | 160 x 160 | 140 x 140 | 1,96 | 1,28 | 2,56 | 87 | 165 | |
| C160 Standard | 180 x 180 | 160 x 160 | 2,56 | 1,98 | 3,24 | 108 | 165 | |
| C160 Eco | 180 x 180 | 160 x 160 | 2,56 | 1,56 | 3,24 | 100 | 165 | |
| R100-150 Eco | 120 x 170 | 100 x 150 | 1,50 | 1,02 | 2,04 | 77 | 165 | |
| R100-150 Standard | 120 x 170 | 100 x 150 | 1,50 | 1,25 | 2,04 | 80 | 165 | |
| R100-200 Eco | 120 x 220 | 100 x 200 | 2,00 | 1,32 | 2,64 | 93 | 165 | |
| R100-200 Standard | 120 x 220 | 100 x 200 | 2,00 | 1,61 | 2,64 | 96 | 165 | |
| R100 - 230 Standard (disponible uniquement en OAC 5,5 et 6,5) | 113 x 241 | 100 x 230 | 2,30 | 1,79 | 2,72 | - | 165 | |
| R100 - 230 Eco (disponible uniquement en OAC 5,5 et 6,5) | 113 x 241 | 100 x 230 | 2,30 | 1,13 | 2,72 | - | 165 | |
| R140-200 Eco | 160 x 220 | 140 x 200 | 2,80 | 1,62 | 3,52 | 106 | 165 | |
| R140-200 Standard | 140 x 200 | 140 x 200 | 2,80 | 2,15 | 3,52 | 114 | 165 | |
| R160-200 Eco | 180 x 220 | 160 x 200 | 3,20 | 1,74 | 3,96 | 113 | 165 | |
| R160-200 Standard | 180 x 200 | 160 x 200 | 3,20 | 2,42 | 3,96 | 121 | 165 | |
| Reference |
Activation pressure |
Thermal fuse cartridge weight in grams |
|
| PCA |
CAI/DD |
PCA |
CAI/DD |
| SL 250 |
SL 550 |
SL 250 |
SL 550 |
SL 250 |
SL 550 |
SL 250 |
SL 550 |
| Vol. total |
Pression (bar) |
Vol. total |
Pression (bar) |
Vol. total |
Pression (bar) |
Vol. total |
Pression (bar) |
Gramme (g.) |
Gramme (g.) |
Gramme (g.) |
Gramme (g.) |
| C100 Eco |
0,67 | 13 | 0,67 | 22 | 0,67 | 16 | 1,05 | 17 | 20 | 20 | 20 | 20 | |
| C100 Standard |
0,67 | 13 | 0,67 | 22 | 0,67 | 16 | 1,05 | 17 | 20 | 20 | 20 | 20 | |
| C120 Eco |
0,67 | 21 | 2,69 | 10 | 1,05 | 17 | 2,69 | 11 | 20 | 40 | 20 | 40 | |
| C120 Standard |
0,67 | 21 | 2,69 | 10 | 1,05 | 17 | 2,69 | 11 | 20 | 40 | 20 | 40 | |
| C140 Standard |
1,6 | 12 | 1,6 | 22 | 4,11 | 10 | 4,11 | 10 | 20 | 40 | 80 | 80 | |
| C140 Eco |
1,6 | 12 | 1,6 | 22 | 4,11 | 10 | 4,11 | 10 | 20 | 40 | 80 | 80 | |
| C160 Standard |
2,69 | 10 | 2,69 | 19 | 2,69 | 12 | 2,69 | 21 | 80 | 80 | 80 | 80 | |
| C160 Eco |
2,69 | 10 | 2,69 | 19 | 2,69 | 12 | 2,69 | 21 | 80 | 80 | 80 | 80 | |
| R100-150 Eco |
0,67 | 17 | 1,05 | 20 | 1,05 | 14 | 2,69 | 10 | 20 | 40 | 20 | 40 | |
| R100-150 Standard |
0,67 | 17 | 1,05 | 20 | 1,05 | 14 | 2,69 | 10 | 20 | 40 | 20 | 40 | |
| R100-200 Eco |
0,67 | 21 | 2,69 | 10 | 1,05 | 17 | 2,69 | 12 | 20 | 40 | 20 | 40 | |
| R100-200 Standard |
0,67 | 21 | 2,69 | 10 | 1,05 | 17 | 2,69 | 12 | 20 | 40 | 20 | 40 | |
| R100 - 230 Standard (disponible uniquement en OAC 5,5 et 6,5) |
1,05 | 15 | 2,69 | 12 | 2,69 | 10 | 2,69 | 13 | 20 | 40 | 40 | 40 | |
| R100 - 230 Eco (disponible uniquement en OAC 5,5 et 6,5) |
1,05 | 15 | 2,69 | 12 | 2,69 | 10 | 2,69 | 13 | 20 | 40 | 40 | 40 | |
| R140-200 Eco |
1,6 | 16 | 4,11 | 12 | 4,11 | 10 | 4,11 | 14 | 40 | 80 | 80 | 80 | |
| R140-200 Standard |
1,6 | 16 | 4,11 | 12 | 4,11 | 10 | 4,11 | 14 | 40 | 80 | 80 | 80 | |
| R160-200 Eco |
2,69 | 12 | 2,69 | 23 | - | - | | - | 80 | 80 | - | - | |
| R160-200 Standard |
2,69 | 12 | 2,69 | 23 | - | - | | - | 80 | 80 | - | - | |
Aluminium cover
- Insulated, light transmission = 0%, heat loss coefficient U = 1.18 W/m².K.
- Non-insulated, light transmission = 0%.
- Opal/Transparent (M4), light transmission = 70%, heat loss coefficient U = 2,8 W/m².K.
- Opal/Transparent (M4 non-dripping) light transmission = 70%, heat loss coefficient U = 2,8 W/m².K.
- Opal (B-S1 d0), light transmission = 62%, heat loss coefficient U = 3.1 W/m².K.
- Transparent (B-S1 d0), light transmission = 85%, heat loss coefficient U = 3.1 W/m².K.
- Calor control (B-S1 d0), light transmission = 55%, heat loss coefficient U = 3.1 W/m².K.
- Grey opaque, light transmission = 0%, heat loss coefficient U = 3.1 W/m².K.
- Opal (B-S2 d0), light transmission = 51%, heat loss coefficient U = 2.8 W/m².K.
- Transparent (B-S2 d0), light transmission = 74%, heat loss coefficient U = 2.4 W/m².K.
- Calor control (B-S2 d0), light transmission = 46%, heat loss coefficient U = 2,4 W/m².K.
C02 thermofuse
- Rated to trip at 93°C (as standard and factory-assembled, delivered with CO2 cartridge).
Electrical switches
- They can be connected to an indicating panel showing the installation's opening position and functional status.
- Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests).
- Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests). RAL tint to be specified in the order.
Painted profiled upstand
- The outer edge of the profiled upstand is protected by a standard RAL 9010 (white) gelcoat; optional painting in most colours in the RAL range (specify in the order).
Part opening pneumatic daily ventilation
- Partial ventilation 300mm with an optional extra cylinder (minimum pressure 6 bar, maximum pressure 8 bar)
Part-opening electrical daily ventilation
- Partial ventilation 300mm with a cylinder (220V)
Pneumatic opening
- Opening is controlled by a pneumatic cylinder.
Profile type
Profile type
Profile type
Profile type
Single flap
SL 250 snow load
- Regulatory snow load for smoke extraction in buildings located between 0 and 400m in altitude. SL 250 = 25 daN/m².
SL 550 snow load
- To exceed regulatory requirements. SL 500 minimum for buildings located between 400 and 800m in altitude.
C02 thermofuse
- Rated to trip at 93°C (as standard and factory-assembled, delivered with CO2 cartridge).
Electrical switches
- They can be connected to an indicating panel showing the installation's opening position and functional status.
Griddle
- Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests).
Painted griddle
- Cylindrical diameter 8: 150mm spacing, satisifies guidelines for the protection of personnel moving on roofs (it has passed the 1200 joules dynamic tests). RAL tint to be specified in the order.
Painted profiled upstand
- The outer edge of the profiled upstand is protected by a standard RAL 9010 (white) gelcoat; optional painting in most colours in the RAL range (specify in the order).
Part opening pneumatic daily ventilation
- Partial ventilation 300mm with an optional extra cylinder (minimum pressure 6 bar, maximum pressure 8 bar)
Part-opening electrical daily ventilation
- Partial ventilation 300mm with a cylinder (220V)
Pneumatic opening
- Opening is controlled by a pneumatic cylinder.
Profile type
- Aluminium cladding.
- Fibre cement.
- Sandwich cladding.
- Steel cladding.
Single flap
SL 250 snow load
- Regulatory snow load for smoke extraction in buildings located between 0 and 400m in altitude. SL 250 = 25 daN/m².
SL 550 snow load
- To exceed regulatory requirements. SL 500 minimum for buildings located between 400 and 800m in altitude.